Empty Socket Test

Empty Socket Test

Summary

A detailed explanation of the Empty Socket Test Option. (NOTE: This option was removed from BPWin beginning with V5.5)

 

Details

During an automated programming system job run, there can be the occasional mis-picks or mis-placements of a device during handling.
The error message for a mis-pick is ALWAYS to manually remove the device and discard.
The error message for a mis-placement is ALWAYS to correct the device placement.

These erros are caused by factors such as poor operator training or aweness, or the operator can neglect to remove a mis-pick from a programming socket.
If this occurs, a double stack can occur in the socket.  If the devices are reprogrammable, then the bottom device is reprogrammed whilst the top device, which is still blank, gets moved to the output.

The Empty Socket Test was created just for this purpose - when the operator fails to do what is required. 

The value for this option will determine how often each programming site will perform a continuity test. We recommend a minimum value of 5. This means that after 5 programming cycles on each site, that site will perform a continuity test. The programming cycles can be passes or failures, and when every fifth device is removed, the site will perform a continuity test. If a device is detected in any socket, anytime throughout the job, the job will be terminated with an error message, stating that a device was detected in a socket that was supposed to be empty.

The logical urge is to set this value to 1 so that if a device is accidentally left in a socket, it will be detected quickly. Although this is true, there are some negative consequences with using a value of 1.
First, you will loose throughput. Devices per hour will decrease due to the added time is takes to perform the continuity test. This decrease can be substantial. 
Second, the site stepper motors will be worked twice as often, which will wear the motors out twice as fast. Replacing the motors require removing the sites, extended down time and site which is removed will require re-teaching.

The reason that we recommend a value of 5 (or 10) is to reduce the drop in devices per hour, and to save wear and tear on the site stepper motors.
Should a failure ever occur, simply rerun the programmed devices in Verify mode to find the blanks.

Again, this option was created to compensate for operator error.

This option works for all socket modules, including FX4.

    • Related Articles

    • Preventative maintenance and cleaning methods for various socket types

      Summary Over the lifetime of a socket various factors can cause the socket performance to degrade. The purpose of this document is to detail preventative maintenance and cleaning methods recommended for various socket types. Adaptsys Support should ...
    • Socket Module Troubleshooting

      Summary Sockets and daughter cards are considered consummables and are not warrantied. BPM Microsystems will warranty the motherboard of the socket module for one year from purchase against defects in workmanship and component failure. This does not ...
    • CyberOptics Image Quality Test

      CyberOptics Camera Image Quality Test This test should be used to ensure that the CyberOptics Laser Align Camera is functioning properly and clear of debris. The test is automatically run at initialization and at the beginning of the job. Various ...
    • Read Socket Insert Count

      How can I use BPWin API to read back the insert count of the installed socket modules? BPWin API does provide insertion counts via "The SystemInformation XML document", which can be retrieved using the "GetSystemInfo" method as well as the ...
    • Automated Socket Modules and Pressure Plates

      For a full list of Automated Socket Modules and the Pressure Plates required to be used on automated handlers, then please view the list here.